Salda Smarty smart home integration, free and open source

Salda Smarty integration for Gladys Assistant

Salda Smarty ventilation over local Modbus TCP: temperatures, mode, fans, filter; optional commands.

Shows a Salda Smarty heat recovery ventilation unit (Smarty 2X, 3X, 4X P/V, MCB controller) in Gladys, through its Modbus TCP interface on your local network, without any cloud or account. Unofficial integration, not affiliated with Salda. Never tested with a real device: it reads and writes the registers Salda publishes, as the open-source pysmarty2 library (used by Home Assistant) does; please report what you see.

Before you start​

  • The unit must be on your network (Ethernet) with Modbus TCP enabled, reachable from Gladys on port 502. Give it a fixed IP address in your router.
  • Modbus TCP has no password: keep the unit on a trusted network.
  • The Modbus unit id (slave address) is 1 unless you changed it on the unit.

Installation​

  1. Install the integration from the Gladys store.
  2. Enter the IP address of the unit (port 502 unless you add one) and, if needed, the Modbus unit id; save.
  3. Open the Discovery tab and add the unit.

What you get​

One device, Salda Smarty ventilation, with:

FeatureNotes
Supply, extract and outdoor air temperatures°C
Supply and extract fan speedsrpm
Filter: days leftdays
Ventilation mode (speed)list: building protection (speed 1), economy (speed 2), comfort (speed 3)
Current modetext: standby, building-protection, economy, comfort, boost
Unit statetext (stable English key, for example economy, boost, change-filters, fire-alarm)
Boost active, alarm, warningread only, 1 = active
Start / stop the boostbuttons

On the Smarty, the mode is the speed: building protection, economy and comfort are speeds 1, 2 and 3. Stand-by (unit stopped) shows in "Current mode" and in the status, never in the list.

The unit is read every 60 s (30 s to 1 h), in four requests over one connection, closed after. The test button, a Discovery scan, a reconnection of Gladys or a restart of the integration never read it sooner than the interval. Reads outside the interval:

  • every command reads the unit just before writing, then reads the value written back;
  • "Stop the boost" and its resends;
  • 5 s and 20 s after a command not confirmed, or after a boost stop that follows a boost start not confirmed;
  • a new address or unit id saved is read at once.

Commands​

Changing the mode and "Start the boost" are refused until Allow the commands is on (off by default). No switch: a voice assistant's "turn everything off" never reaches the ventilation.

  • Every command reads the unit again just before writing (the mode, the unit state, its versions and the value to change), writes nothing when the value is already right, and is confirmed only when the unit returns the echo of the write and then reads the value asked. A command that may have reached the unit without being confirmed answers "sent, without confirmation": check the unit a few seconds later. A command the unit refuses with Modbus exception 1, 2 or 3 (illegal function, address or value) answers "refused" and was not applied; other exceptions (device failure, busy…) answer "sent, without confirmation". A command that cannot be written within 3.5 s is refused and nothing is sent.

  • Unit in stand-by (stopped): changing the mode or starting the boost would start it, so they are refused as soon as the mode set, the current mode or the state read is stand-by. Gladys neither stops nor restarts the unit in this version (stopping a heat recovery unit stops the air renewal).

  • Unit stopping (state "cooling heaters" or "closing dampers", Salda's stop sequence): the same refusals.

  • Critical or fire alarm (unit state): changing the mode and "Start the boost" are refused. The "Alarm" feature (alarm A) alone does not block them.

  • Versions changed: the integration keeps the software and configuration versions of the unit. When they change (an update, or another device at the same address), the status says so and changing the mode and "Start the boost" are refused until Test the connection is pressed, which accepts the versions shown. Unreadable versions block nothing.

  • Stop the boost is not subject to the option, another command, a read in progress, stand-by, an alarm or the versions; it cancels a command not sent yet. A refused or closed connection, a missing or wrong answer are tried again every 250 ms until 3.5 s after the press. It can still answer without having stopped the boost in these cases:

    • no valid address or unit id in the configuration;
    • a value other than 1;
    • the unit unreachable until 3.5 s after the press ("not sent", or "not sent yet" while it still tries);
    • the unit refusing the write (Modbus exception 1 to 3: "refused");
    • the echo or the read back missing or different, another Modbus exception, or the boost read still on ("sent, without confirmation");
    • another address or unit id saved during the stop: it is interrupted ("sent, without confirmation" if it had left) and its resends are dropped.

    A second press during the first joins it. When not confirmed, the reads of the next two minutes send it again (three times at most) while the boost stays on; a "Start the boost" sent afterwards wins and is never undone. After a "Start the boost" sent but not confirmed, that start may still be applied after the stop: the stop is then watched for two minutes even when confirmed (reads at 5 s and 20 s, resent when the boost reads on, three times at most), and this watch survives a restart of the integration.

  • The Smarty limits the boost duration itself.

Limits​

  • Only the registers Salda publishes and pysmarty2 uses are read and written (no filter timer reset nor alarm reset in this version).
  • The Smarty's Modbus map gives no serial number: the integration shows one unit, the one at the address entered, and only checks its versions (see above), which two units may share. Changing the address keeps the device and its history; another unit with the same versions put at the same address would show on the same device and receive its commands too. Reserve the address in your router (fixed DHCP lease).
  • Temperatures are read as signed values (tenths of a degree); a value outside -60 to 90 °C is ignored.
  • Gladys opens only one Modbus connection at a time to the unit; another home automation system polling it meanwhile may slow its answers.
  • An invalid address is never shown again in the status: only its number of characters.

Privacy​

Nothing leaves your network. The integration only keeps in its /data volume the time of its last read, the versions of the unit and, for two minutes at most, the watch of a boost stop.

Configuration settings​

These are the settings Salda Smarty asks for in its configuration screen in Gladys.

SettingTypeRequiredDescription
Your Salda Smarty unitsectionNoShows your Salda Smarty heat recovery ventilation (Smarty 2X, 3X, 4X P/V) in Gladys through its Modbus TCP interface (port 502) on your local network, without any cloud: supply, extract and outdoor temperatures, mode, unit state, fan speeds, days left before the filter change, alarm, warning and boost. Enable Modbus TCP on the unit, enter its IP address (give it a fixed address in your router), save, then add the unit from the Discovery tab. The mode (which sets the fan speed) and the boost can be changed from Gladys only if you allow the commands below; stopping the boost never depends on that option (see the guide for the cases where it can fail). Gladys never stops nor restarts the unit. Modbus TCP has no password: keep the unit on a trusted network. Never tested with a real device. Not affiliated with Salda.
IP address of the unitstringYesAn IPv4 address or a host name (port 502 unless you add one, for example 192.168.1.80:502).
Modbus unit idnumberNoThe Modbus slave address of the unit, 1 unless you changed it on the unit.
Allow the commandsbooleanNoOff by default. On: Gladys may change the mode (building protection, economy, comfort: the fan speed) and start the boost; both are refused on a unit in stand-by, stopping, or in critical or fire alarm. Off: these commands are refused. Stopping the boost never depends on this option.
Refresh interval (s)numberNoHow often the unit is read, in seconds.
Language of the feature namesselectNoUsed for the names of the device and features added from now on, the status and the command errors.

How to install Salda Smarty in Gladys​

  1. In Gladys, open Integrations: Salda Smarty appears in the catalog, next to the native integrations, with a community badge.
  2. Click Install. Gladys pulls the Docker image (ghcr.io/lm1lc3n7/gladys-salda-smarty:0.1.1), starts it in a sandbox isolated from the core, and generates the integration's interface (devices, discovery and configuration).
  3. Open the Configuration screen of the integration, fill in the settings, and save.
  4. You can also install it directly from its repository URL: https://github.com/LM1LC3N7/gladys-salda-smarty.

Salda Smarty requires Gladys >=5.1.0. The catalog inside Gladys refreshes every hour, so a new version becomes available at most one hour after its release.

Not running Gladys yet? It is free and open source: follow the installation guide to get started.

About external integrations​

Salda Smarty is an external integration: a community integration packaged as a Docker container and published on GitHub, that Gladys installs in one click and runs in a sandbox isolated from its core. It is published and maintained by LM1LC3N7, not by the Gladys core team.