BACnet/IP integration for Gladys Assistant

Read and write the objects of a BACnet/IP device: air handling units, heat pumps, controllers.

Reads and writes the objects of a BACnet/IP device: air handling units, heat pumps and chillers, room and plant controllers, meters, BACnet gateways (Siemens Desigo, Daikin, Flexit, Distech, Honeywell...). Each object you declare becomes a feature of one Gladys device.

Developed without real building equipment: tested against the bacnet-stack demo server. Feedback welcome, on the forum or in the issues of the repository.

What you get​

  • One Gladys device per BACnet device, one feature per declared object: analog objects as numbers with their unit (temperature, humidity, pressure, CO2, power, energy in kWh...), binary objects as on/off, multi-state objects as a state number or as the text of the state ("Comfort", "Night").
  • The values read at the interval you choose, only the changes sent to Gladys.
  • Writing, off by default: on/off and temperature setpoints from the dashboard, "Write a value" and "Release a priority" for any declared object, at the BACnet priority you choose.
  • Scene triggers when the device is lost or back, and when an object goes into alarm or fault.
  • A dashboard widget with the first values and the health of the link.

Compared with the Flexit integration (LM1LC3N7/gladys-flexit), made for Flexit ventilation units with their objects already mapped, this one talks to any BACnet/IP device: you choose the objects.

Requirements​

  • Gladys Assistant 5.1 or later.
  • A device that speaks BACnet/IP (UDP, port 47808 by default) with a fixed IP address, reachable from the Gladys server. BACnet MS/TP (RS-485) devices need a BACnet/IP router or gateway.
  • Its device instance, if the device does not give it (most do).

Configuration​

Integrations → BACnet/IP → Configuration. Save after each step: the status at the top of the screen says whether the device answers.

Device​

  • IP address: the address of the device or of its BACnet/IP gateway. A port other than 47808 can follow it (192.168.1.50:47809) or go in UDP port.
  • Device instance: leave it empty, the integration reads it from the device (wildcard instance 4194303). Enter it when the device does not answer that request, or behind a gateway that serves several devices.

The integration sends its requests to this address only (unicast): Gladys runs it on a bridge network, where a Who-Is broadcast does not reach the building network. There is no automatic discovery.

Objects​

Press List the objects: it reads the object list of the device and gives the analog, binary and multi-state objects with their name, ready to copy. Then fill Objects, entries separated by semicolons:

Name: type:instance [kind] [write] [options]
Supply air: ai:1; Extract air: ai:2; Fan: bo:1 switch; Mode: msv:1 text
  • Name (optional, followed by a colon and a space): the name of the feature. Without it, the objectName of the device is used.
  • type:instance: analog-input:1 or ai:1, analog-output (ao), analog-value (av), binary-input (bi), binary-output (bo), binary-value (bv), multi-state-input (msi), multi-state-output (mso), multi-state-value (msv). AI1 and OBJECT_ANALOG_INPUT:1 work too.
  • kind (optional): by default it follows the BACnet units of the object (°C → temperature, %RH → humidity, Pa → pressure, kWh → energy...). Kinds: temperature, humidity, pressure, co2, illuminance, power, energy, voltage, current, volume, duration, value (any number), setpoint (writable temperature), binary, switch (writable on/off), state (number of the state), text (text of the state).
  • write: the object may be written (outputs and values only: BACnet inputs are not writable).
  • Options: unit= (°C, %, Pa, kPa, bar, ppm, W, kW, Wh, kWh, V, A, L, m3, s, min, h...), scale= and offset= (value × scale + offset), min= and max= (bounds of a write and of the gauge), precision= (decimals).

Up to 100 objects. Check the configuration lists the mistakes entry by entry. Then add the device from the Discovery tab.

Reading interval​

Every 10 s, 30 s (default), 1 min or 5 min, with one ReadPropertyMultiple request per 8 objects; devices without that service are read property by property. Gladys accepts 300 values a minute: with many objects, the interval grows (100 objects: every 25 s at least).

Writing​

Turn on Allow writing, and declare write the objects Gladys may change. Writing a wrong object can stop or damage an installation: declare only what Gladys must change, and check with the installer.

BACnet commands outputs and values through 16 priorities: 1 is the highest (life safety), 16 the lowest. The value with the highest priority wins; a value written at a priority stays until it is released. Write priority is 8 (manual operator) by default; avoid 1 to 5. Releasing a priority (writing null) gives control back to the next priority, or to the default value of the object. Objects without a priority array (many analog and binary values) take the value directly and have nothing to release.

From the dashboard, only switch and setpoint objects are controls (an on/off input and a target temperature, never a voice-controlled switch or thermostat). Every other declared object is written with the actions. A setpoint without min= and max= is held to 0–100 °C (32–212 °F).

Actions​

  • List the objects: up to 60 usable objects with their name.
  • Check the configuration: whether the device answers, and the mistakes.
  • Write a value: an object (its name or av:3), a value (a number, 0 / 1 or on / off, a state number or its text), an optional priority.
  • Release a priority: an object and an optional priority.

Scenes​

  • Triggers: The BACnet device is lost (with the error), The BACnet device is back, A BACnet object goes into alarm (statusFlags in alarm or fault, once until it clears; the object name and the flag are variables).
  • Actions: Write a BACnet object and Release a BACnet priority, same fields as the buttons. A refusal fails the action, not the scene.
  • Every feature also works with the usual Gladys device triggers (a temperature above a threshold, a fan that stops).

Dashboard​

The BACnet device widget shows the first six values of the device and a status block: whether the device answers, the objects in alarm or fault, the time of the last value. The status block can be hidden in the widget settings.

Limits​

  • No Who-Is discovery, no COV subscription: the values are polled.
  • One BACnet device per installation of the integration.
  • Only analog, binary and multi-state objects; no schedules, trends, calendars or alarm acknowledgment.
  • No BBMD or foreign device registration: the device must be reachable in unicast from the Gladys server.
  • The integration listens on UDP port 47808 inside its container. A device that answers to port 47808 of the sender instead of the port the request came from may not get through the address translation of Docker.

Troubleshooting​

  • "Does not answer": check the address and the port, that BACnet/IP is on in the device, and that no firewall blocks UDP 47808 between Gladys and the device.
  • "No such instance": empty Device instance, or enter the one shown by the installer's tool.
  • An object "does not exist": compare with List the objects.
  • "The device refused the write (write-access-denied)": the object is read-only, or out of service, or the device needs a password.
  • Full detail with the variable LOG_LEVEL=debug in the integration logs.

Credits​

  • @bacnet-js/client (MIT), the BACnet stack in JavaScript maintained by Innovation-System, a fork of node-bacstack by Fabio Huser.
  • bacnet-stack by Steve Karg, whose demo server was used for the tests.
  • BACnet® is a registered trademark of ASHRAE. This integration is not affiliated with ASHRAE nor with any device maker.

Configuration settings​

These are the settings BACnet/IP asks for in its configuration screen in Gladys.

SettingTypeRequiredDescription
Getting startedsectionNoEnter the IP address of the BACnet/IP device, save, then use "List the objects" to find their identifiers. Declare the objects you want in the Objects field, save again, and add the device from the Discovery tab: each object becomes a feature, read at the chosen interval.
Language of the messagesselectNoUsed for the texts given to the scenes.
DevicesectionNoGive the device a fixed IP address: Gladys reaches it in unicast, a Who-Is broadcast does not leave the integration's network.
IP addressstringNoThe IP address of the BACnet/IP device (or of its BACnet/IP gateway).
UDP portnumberNo47808 (0xBAC0) on almost every device.
Device instancenumberNoEmpty: read from the device. Enter it if the device does not give it (or behind a gateway serving several devices).
ObjectssectionNoUp to 100 objects. Writing a wrong object can stop or damage an installation: declare "write" only what Gladys must change.
ObjectsstringNoEntries separated by semicolons: Name: type:instance, then kind, write and options. Types: analog-input (ai), analog-output (ao), analog-value (av), binary-input/output/value (bi, bo, bv), multi-state-input/output/value (msi, mso, msv). Kinds: temperature, humidity, pressure, co2, illuminance, power, energy, voltage, current, volume, duration, value, setpoint, binary, switch, state, text (default: from the BACnet units). Options: scale= offset= unit= min= max= precision=.
Reading intervalselectNoHow often the objects are read. Gladys accepts 300 values a minute: with many objects, they are read less often.
WritingsectionNoBACnet commands outputs and values through 16 priorities: 1 is the highest (life safety), 16 the lowest. A value written at a priority stays until it is released.
Allow writingbooleanNoOff by default. When on, only the objects declared "write" (or switch, setpoint) can be changed from Gladys, and only if the device allows it.
Write prioritynumberNo1 to 16; 8 (manual operator) by default. Avoid 1 to 5, kept for safety functions.

How to install BACnet/IP in Gladys​

  1. In Gladys, open Integrations: BACnet/IP appears in the catalog, next to the native integrations, with a community badge.
  2. Click Install. Gladys pulls the Docker image (ghcr.io/guim31/gladys-bacnet:1.0.0), starts it in a sandbox isolated from the core, and generates the integration's interface (devices, discovery and configuration).
  3. Open the Configuration screen of the integration, fill in the settings, and save.
  4. You can also install it directly from its repository URL: https://github.com/guim31/gladys-bacnet.

BACnet/IP requires Gladys >=5.1.0. The catalog inside Gladys refreshes every hour, so a new version becomes available at most one hour after its release.

Not running Gladys yet? It is free and open source: follow the installation guide to get started.